Description
The main earth fault protection relays in distributions systems, power stations & large manufacturing / processing plants can fail to detect a high impedance breakdown to earth causing hazard to human life & potential damage to plant & equipment. In these & other situations demanding extra sensitive earth fault protection, the 2P49 relay using solid state techniques, can be applied to detect earth currents down to 0.5% of the CT nominal current.
Features
-
High sensitivity
-
Detects phase angle imbalance
-
Detects negative phase sequence
-
Detects supply undervoltage
-
Unaffected by frequency variations of + 5Hz
-
Adjustable 5-15% out of balance setting
-
Range of detection voltages & frequencies available
-
No auxiliary voltage required
-
Fail safe operation (Contact normally picked up)
-
Filter rejects harmonics & control tones
-
Size 2M28-S draw out case
-
Standard heavy duty contacts
-
Optional mechanical flag indication
-
Optional 2s approx. time delay on drop off function
-
Made in Australia